Description
The Power-Sure 700 Three Phase Power Line Conditioning system provides exceptional system reliability that can be attributed to MGE's microprocessor controlled zero-current cross tap switching technology. The Power-Sure 700 combines solid state, microprocessor based voltage regulation, with a multi-shield computer grade transformer and filter to remove transients and noise. The combined effect is a regulating and shielded isolation transformer/system that solves 99% of the electrical disturbance problems. The Power-Sure 700 protects your system against electrical brownouts, sags, surges, transients and other electrical disturbances. This power conditioner also provides the protection, efficiency, and reliability that are critical to every application with sensitive equipment.
Main Features
Protection Type: Transient
Protection Type: AC Noise
Protection Type: Brownout
Protection Type: Sag
Protection Type: AC Surge
Protection Type: Overload
Protection Type: Over Voltage
Input Voltage: 208 V AC
Output Voltage: 120 V AC
Temperature: 14°F (-10°C) to 104°F (40°C) Operating
Altitude: Up to 10000 ft
Form Factor: Tower
Dimensions: 77" Height x 56" Width x 41.50" Depth
Weight (Approximate): 4000 lb
Additional Information: 300kVA Input voltage range: +10% to -20% Output voltage range: ±3% Typical Efficiency: 97% Typical, 95% minimum Load power factor: 0.6 leading to 0.6 lagging Common-mode noise attenuation: 140 dB Normal-mode noise attenuation: -3 dB @ 1000 HZ, -40dB per decade Total harmonic distortion: Less than 1% added Correction time: 1 Cycle typical, 1.5 Cycle maximum Overload rating: 200% for 10 seconds, 1000% for 1 cycle Audible noise: Less than 50dBA @1 meter (depending on size)
Certifications & Standards: UL 1012 CSA FCC Class A certified
Standard Warranty: 1 Year