Eaton Power-Sure T800F-05000 Line Conditioner

Eaton Power-Sure T800F-05000 Line Conditioner (T800F-05000)

$7,420.97 Out of Stock
Quantity:

Description

Every facet of our daily life is being automated by faster microprocessors and microprocessor-based equipment which require steady continuous power. As market pressures force the deregulation of the electrical industry, utility companies have less and less control over the quality of power supplied to sensitive electronic equipment. In data processing and medical applications, the effects of unreliable power can be translated into incorrect data, lost memory, premature component failure, mixed and garbled data and inaccurate diagnostics. Power conditioning alleviates these problems. For this reason, the Power-Sure 800 was designed using a special high "K-Factor" transformer capable of handling these harmonics without overheating. The Power-Sure 800 has one of the highest "K-Factors" in the industry. Additionally, the Power-Sure 800 virtually eliminates any transient harmonics being reflected back onto the power lines, thus preventing damage to building wiring.

Main Features

  • Protection Type: AC Surge
  • Protection Type: AC Noise
  • Protection Type: Harmonics
  • Temperature: -4°F (-20°C) to 104°F (40°C) Operating
  • Form Factor: Floor-mountable
  • Dimensions: 724 mm Height x 508 mm Width x 584 mm Depth
  • Weight (Approximate): 185 kg
  • Additional Information:
  • VA Rating: 5000VA
  • Watt Rating: 5000W
  • AC 120/208/240/480 V - 5 KW
  • Line Regulation: +/- 2% VOut for +10% to -20% V In at 100% Load
  • Load Regulation: +/-3% for 0% to 100% load
  • Immunity to Distortion: @ 40% THD V In, 5% Max THD VOut
  • Ride-through Capability: 1 cycle
  • Voltage Recovery: 2 cycles to 95%, 3 cycles to 100%
  • K-Factor: K-30 Rated
  • Power Factor Correction: Input of 0.95 typical
  • Harmonic Attenuation: -23dB for load reflected harmonics
  • Galvanic Isolation: NEC 250-5d, 0.001 pf
  • Surge Protection: UL 1449 Rating 330 V, ANSI/IEEE 62.41-Cat B3
  • Common Mode Noise Attenuation: 140 dB
  • Transverse Mode Noise Attenuation: 120 dB
  • Reliability: 200,000 hours (MTBF)
  • Audible Noise: 52dB to 56dB measured at 1 meter, A Scale
  • Efficiency: Approx. 92% at full load
  • Certifications & Standards:

    Safety: Underwriters Laboratories UL 1012 - UL 544 - cUL

  • Standard Warranty: 2 Year
  • General Information

    Product TypeLine Conditioner
    Brand NameEaton
    ManufacturerEaton Corporation
    Product ModelT800F-05000
    Product NamePower-Sure 800 T800F-05000 Line Conditioner
    Product LinePower-Sure
    Manufacturer Part NumberT800F-05000
    Manufacturer Website Addresswww.eaton.com/EatonCom/Markets/NorthAmerica
    Marketing Information

    Every facet of our daily life is being automated by faster microprocessors and microprocessor-based equipment which require steady continuous power. As market pressures force the deregulation of the electrical industry, utility companies have less and less control over the quality of power supplied to sensitive electronic equipment. In data processing and medical applications, the effects of unreliable power can be translated into incorrect data, lost memory, premature component failure, mixed and garbled data and inaccurate diagnostics. Power conditioning alleviates these problems. For this reason, the Power-Sure 800 was designed using a special high "K-Factor" transformer capable of handling these harmonics without overheating. The Power-Sure 800 has one of the highest "K-Factors" in the industry. Additionally, the Power-Sure 800 virtually eliminates any transient harmonics being reflected back onto the power lines, thus preventing damage to building wiring.

    Technical Information

    Protection TypeHarmonics

    Environmental Conditions

    Temperature-4°F (-20°C) to 104°F (40°C) Operating

    Physical Characteristics

    Form FactorFloor-mountable
    Dimensions724 mm Height x 508 mm Width x 584 mm Depth
    Weight (Approximate)185 kg

    Miscellaneous

    Certifications & Standards

    Safety: Underwriters Laboratories UL 1012 - UL 544 - cUL

    Additional Information
  • VA Rating: 5000VA
  • Watt Rating: 5000W
  • AC 120/208/240/480 V - 5 KW
  • Line Regulation: +/- 2% VOut for +10% to -20% V In at 100% Load
  • Load Regulation: +/-3% for 0% to 100% load
  • Immunity to Distortion: @ 40% THD V In, 5% Max THD VOut
  • Ride-through Capability: 1 cycle
  • Voltage Recovery: 2 cycles to 95%, 3 cycles to 100%
  • K-Factor: K-30 Rated
  • Power Factor Correction: Input of 0.95 typical
  • Harmonic Attenuation: -23dB for load reflected harmonics
  • Galvanic Isolation: NEC 250-5d, 0.001 pf
  • Surge Protection: UL 1449 Rating 330 V, ANSI/IEEE 62.41-Cat B3
  • Common Mode Noise Attenuation: 140 dB
  • Transverse Mode Noise Attenuation: 120 dB
  • Reliability: 200,000 hours (MTBF)
  • Audible Noise: 52dB to 56dB measured at 1 meter, A Scale
  • Efficiency: Approx. 92% at full load
  • Warranty

    Standard Warranty2 Year